The longest extension cord
Ontario's biggest generating stations are often far from the cities that use the most electricity. Energy from northern hydroelectric stations and from nuclear stations on the shores of Lake Ontario and Lake Huron must travel tens or hundreds of kilometres. Every metre of wire has some resistance, so some energy is always lost as heat. The trick that keeps those losses small is to use transformers to send the energy at very high voltage.
Why high voltage? The I²R problem
A power line has a resistance R. The current I in it heats the line. The power wasted is
P_loss = I²R
The power a station sends is P = VI. For the same power, a higher voltage means a lower current: I = P ÷ V.
- Raise the voltage 10 times and the current falls to 1/10.
- The loss depends on I squared, so it falls to (1/10)² = 1/100.
That is why transmission lines run at hundreds of thousands of volts. Hydro One's main transmission lines in Ontario run at voltages such as 230 kV and 500 kV.
Careful: in P_loss = I²R, use the current in the line and the line's resistance. Do not use V²/R with the station voltage; the station voltage is not the voltage across the line wires.
Why AC?
High-voltage transmission only works if the voltage can be stepped up at the station and stepped down again near customers. Transformers do this simply, efficiently and with no moving parts, but they need a changing current: AC. That is the main reason the grid uses AC.
Other reasons: AC generators are simple and robust, and AC is easy to switch off safely because the current passes through zero 120 times a second.
DC does have a niche. For very long distances, or for undersea cables, high-voltage DC (HVDC) lines can lose less energy than AC lines. They need expensive converter stations at each end to change AC to DC and back, so they are used only for special links.
Stepping down to your home
At transformer stations near cities, large transformers step the voltage down for distribution lines along streets. A local transformer on a pole or in a green box on a lawn then steps it down to the 120 V / 240 V supply in your home. Lights and most outlets use 120 V; stoves, dryers and some heaters use 240 V.
Hands-on activityModel transmission losses
You need: paper, a calculator, and (optional) a spreadsheet.
- A station must deliver 50 MW through lines with a total resistance of 4.0 Ω. Make a table with columns: transmission voltage, line current, power lost, percent lost.
- Fill it in for 25 kV, 50 kV, 115 kV, 230 kV and 500 kV.
- Graph percent lost against voltage. Describe the shape.
- Look outside on a walk: can you spot a pole-top or lawn transformer near your home? Count how many houses seem to be connected to it. Grown-up note: look only; never touch or climb near poles, lines, green transformer boxes or fences around transformer stations.
What to look for: at 25 kV, I = 2000 A and P_loss = 16 MW (32%); at 50 kV, 1000 A and 4.0 MW (8.0%); at 115 kV, about 435 A and 0.76 MW (1.5%); at 230 kV, about 217 A and 0.19 MW (0.38%); at 500 kV, 100 A and 0.040 MW (0.080%). The loss falls very steeply as voltage rises (proportional to 1/V²). One local transformer often serves several homes.